AIRPURION 2501 / 2
...is characterized by an extraordinarily high disinfection performance with a compact design and low energy consumption. It is designed in accordance with applicable laws, standards and directives.
The AIRPURION 2501 /2 consists of two PURION 2501 reactors that must be installed in series. The introduced air is passed through the reactors and disinfected. The unit can be easily integrated into pipeline systems, even retroactively.
The system can optionally be equipped with lifetime monitoring (OTC – Operating Time Counter) with potential-free contacts.
The control unit is integrated into an electrical cabinet, which can optionally be made of stainless steel. The electrical cabinet is standardly equipped with a “total signal error message.” In case of a UV system failure, a red indicator light on the cabinet door will illuminate, and at the same time, this error can be externally evaluated (potential-free contact). The function of each UV lamp is indicated by a green indicator light.
The compact design allows for easy and tool-free lamp removal and replacement, for example, at the end of the emitter’s useful life.
Optionally, the PURION 2501 /2 duct unit can be equipped with the PURION mounting set AIRPURION 2001 – 2501. This enables easy and space-saving wall mounting if needed.
Technical Data
Manufacturer | PURION GmbH |
Type | AIRPURION 2501/2 |
Disinfection Performance 99% | up to 100 m³/h air |
Dimensions H x W x D in mm: Reactor Control Cabinet H x W x D : | 928 x 186 x 85 600 x 600 x 210 |
Number of Reactors | 2 x PURION 2501 |
External Thread Connection | R 1 1/2“ |
Max Temperature | 60 C° / 90 C° |
Bulb Lifetime | 8,000 - 10,000 h |
Number of Bulbs | 2 |
Enclosure Protection Class | IP 54 |
Electrical Connection | L/N/PE 50 Hz 230V |
Power | 2 x 90W (up to 60 C°) 2 x 106W (up to 90 C°) |
Fuse Protection | 1 x 6A |
Details of Disinfection Performance:
max. Airflow | ||
guaranteed UVC Dose1 | 60% Humidity | 90% Humidity |
30 J/m² | 100 m³/h | 60 m³/h |
90 J/m² | 35 m³/h | 20 m³/h |
This system is used in:
Air Disinfection in the Beverage Industry |
Chemical Industry with Organic Materials/Operational Fluids |
Ventilation Concepts for the Cleanroom Industry |
Advantages:
- No chemical input
- No odor or taste alteration
- Low maintenance operation
- Low operating costs
Download Data Sheet
1Adose of 30 J/m² ensures 99% disinfection for light to medium contamination, e.g. by Ecoli, Salmonella; a dose of 90 J/m² ensures 99% disinfection for medium to high contamination, e.g. by influenza viruses, brown yeast and listeria.